Uncategorized
Update PDU firmware on Exadata Database Machine
In this article we will demonstrate how to update the Power Distribution Unit (PDU) firmware on Exadata Database Machine
You may update the firmware on a PDU if you are running an older version in some cases you need to update the firmware after replacing a hardware component.
Get the current PDU Firmware version
Under “System Info”, look for “Firmware Version”. You may update the firmware on a PDU if you are running an older version in some cases you need to update the firmware after replacing a hardware component.
Get the current PDU Firmware version
- Using a web browser login to the PDU using the hostname or IP address
- Click on “Module Info”
In my case the PDU firmware version is 2.01.
Steps to Upgrade PDU firmware version
- Login to My Oracle Support and open the MOS note 888828.1
- Under the MOS note 888828.1 go to the section “Power Distribution Unit (PDU) metering unit”
- Download the latest PDU patch available. In this case it is 28529456
- Unzip the patch zip file in a location on your desktop or laptop
- You will see 2 files after unzipping the patch
- Using a web browser login to the PDU using the hostname or IP address
- Click on “Net Configuration”
- Enter the username and password. Default username and password is admin/admin
- Click on “Firmware Update”
- Click on the Browse button and select the MKAppl_V2.09.DL file that was created after unzipping the patch above
- Click on the Submit button to update the metering unit firmware
- We can now see the file is being uploaded
- After Firmware Update is complete & PDU Restart. Wait for couple of minutes.
- Click on the Module Info link to verify the firmware updated version and confirm that the firmware updated successfully.
- Click on Logout
- Repeat the above steps on second PDU in the Exadata Rack.
Conclusion
In this article we have learned how to update the PDU firmware on an Exadata Database Machine.
4 Comments
Anonymous
Good one. BTW all this is online?
Syed Waheed (DBA)
Yes
netsoftmate
There are 2 PDUs in Exadata Rack. You will be doing it one at a time. So it will be rolling online.
Satya
Hi
From the above link could see / view images Can you check and do the needful.